Detailed explanation of the principle of the function of the seismic support and hanger system
As we all know, the role of traditional supports and hangers in electromechanical systems is load-bearing. The principle is the common sense that gravity acts downward. How does the seismic supports and hangers play a role in earthquake resistance?
Through GB 50981-2014 "Code for Seismic Design of Building Electromechanical", we can know that the seismic support and hanger is mainly through the function of resisting horizontal seismic force to ensure the safety of the support and hanger system.
How to understand "resisting horizontal seismic force"?
1. How does the earthquake work and how does the vibration cause damage to the building?
First, we need to know what an earthquake is. According to the explanation of Baidu Encyclopedia, we can know that an earthquake is a vibration caused by the release of energy from the earth's crust, which affects or even destroys human life through seismic waves.

According to the current level of earthquake research in the world, seismic waves can be divided into three forms: longitudinal wave (P wave), transverse wave (S wave), and surface wave (L wave). The longitudinal wave belongs to the propulsion wave, which makes the ground vibrate up and down, and the destruction is relatively weak. The transverse wave belongs to the shear wave, which causes the ground to shake around and around, and is more destructive. Surface wave belongs to the mixed wave generated by the excitation of longitudinal wave and transverse wave after meeting on the surface, which is the most destructive.
In the field of mechanical and electrical seismic, popular understanding is: gravity supports and hangers play a role in resisting and alleviating vertical seismic forces (I. e. longitudinal waves). The seismic support and hanger, through its unique diagonal structure, greatly resist and alleviate the horizontal seismic force (I. e. transverse wave).
2. The action mode of seismic supports and hangers, and how seismic diagonal braces resist horizontal seismic forces
As we all know, seismic supports and hangers are reinforced by seismic braces to play a seismic role.
It is precisely because of the existence of seismic braces that the pipeline support and hanger system, which is originally unbound in the horizontal direction, can be safe and reliable when an earthquake occurs, and prevent the pipeline support and hanger system from collapsing and falling, causing serious secondary disasters.
From a simple mechanical point of view, we can do a simple disassembly analysis of seismic braces.
From the above figure, we can obviously see that the seismic diagonal brace has an oblique upward pulling force on the overall bracket. According to the force decomposition principle, the oblique upward pulling force can be decomposed into a horizontal force Fx and a vertical force Fy. The horizontal force is the load effect value of horizontal earthquake action, and the vertical force is the load effect value of gravity action.
Applied to practice, the seismic brace to play a "seismic" function, but also in accordance with the above principle. If the anti-seismic brace is not set, the pipeline support and hanger system is not bound in the horizontal direction. Once an earthquake occurs, it can be imagined that the overall support and hanger system will produce disordered irregular shaking, which will gradually break and fall off at the rooting or connecting nodes of the structure, resulting in irreparable losses.

3. Whether the seismic effect of the diagonal brace is related to the bearing gravity, and whether there is gravity on the diagonal brace
From the second point, we can know that the seismic diagonal brace has a certain gravity load effect in mechanics. Of course, the greater the gravity carried by the pipeline support and hanger system, the greater the gravity effect on the seismic brace, so there is indeed a certain relationship between the seismic effect of the brace and the bearing gravity.
However, one thing we need to pay attention to is that the functionality of seismic supports and hangers is mainly "seismic" rather than "bearing". The premise of seismic support and hanger installation is that the gravity support and hanger must meet the conditions and can meet the gravity effect of all pipelines and media in the vertical direction, that is, the gravity effect on the seismic support and hanger can meet the functional requirements. In layman's terms, it can be summarized as follows: there is gravity on the seismic brace, but when we design and calculate, we do not consider the gravity effect of the seismic support and hanger, that is, we do not consider the gravity co-frame. (Except for special cases, some places with small spaces may have gravitational co-frames.)
4. Functional analysis of seismic connectors
Seismic connectors generally have the following forms

From the above, we can know that the seismic connection components are basically in the form of hinges, which provide a similar buffer function when an earthquake occurs, so as to avoid the breakage that may be caused by the pure rigid connection.
Seismic connection components and concrete building structures connected to the place, generally used after the expansion of the bottom of the anchor, this type of anchor has a good anchoring effect, higher than the regular expansion bolt connection strength.
The composition of the building's electromechanical seismic system includes riser pipe bundles, steel beams and purlin clamps, ring pipe hangers, shockproof diagonal bracing systems, shockproof steel hangers and supports, etc.
The surface of the base material in the anchorage zone shall be solid and smooth, and there shall be no defects affecting the anchorage bearing capacity such as sand lifting, shell lifting, honeycomb, pitting surface and oil activity;
The strength grade of concrete shall reach C30 or above within the scope of anchorage depth;
Anchoring operation shall meet the design requirements of anchor bolts. Before drilling, steel bar detectors shall be used for inspection to avoid hidden objects such as steel bars and conduits.
Seismic supports and hangers fixed on steel columns and steel beams shall be connected by special clamps.
The verticality deviation of the installed full-threaded boom shall not be greater than 4 degrees.
When the connecting nut is connected with the full-threaded hanger rod and anchor bolt, the threaded end shall be drawn according to the screwing depth, and the screwing depth shall reach 45% of the connecting nut length:
The distance between the inclined brace of single pipe anti-seismic support and hanger shall not exceed 10cm;
The connection between the pipe clamp and the pipeline shall be provided with shockproof insulating rubber pad to prevent electrochemical corrosion at the connection, and the connection between the pipe clamp and the pipeline shall be stable:
The screw nut shall be locked according to the design torque to prevent loosening.
seismic bracket design process:
The fabricated/finished bracket system is a bracket product that is assembled on the site with factory prefabricated parts, using standard connectors and standard channel steel, as shown in the following figure:

The acceptance and quality of assembled/finished bracket products and supporting anchor bolt products shall meet (not limited to) the requirements of the following standards and current national codes and standards:
GB50011-2010 Code for Seismic Design of Buildings
GB50981-2014 Code for Seismic Design of Mechanical and Electrical Engineering of Buildings
GB50242-2002 Code for Construction Quality Acceptance of Building Water Supply and Drainage and Heating Engineering
GB50234-2002 Code for Acceptance of Ventilation and Air Conditioning Engineering Quality
GB50261-2005 on Code for Construction and Acceptance of Automatic Sprinkler System
GB50303-2002 of Code for Acceptance of Construction Quality of Building Electrical Engineering
03S402 Indoor Pipe Support and Hanger
Note: The above specification requirements have been updated.
seismic bracket specification:
GB50011-2010:
Article 1.0.2 Seismic design must be carried out for buildings in areas with seismic fortification intensity of 6 degrees and above.
3.7.1 Non-structural components, including building non-structural components and building ancillary mechanical and electrical equipment, themselves and their connections with the main body of the structure shall be subject to seismic design.
Chapter 13: Calculation and seismic measures for seismic design of non-structural members.
GB50981-2014:
1.0.4 Seismic fortification intensity of 6 degrees and more than 6 degrees of building mechanical and electrical engineering must be seismic design.
Article 5.1.4 Anti-seismic supports and hangers shall be used for smoke and exhaust air duct, accident ventilation air duct and related equipment.
Article 7.4.6 The common antenna set on the roof of the building shall adopt the safety protection measures to prevent the equipment or parts from falling and injuring people due to the damage caused by the earthquake.
The GB50981-2014 specifies the setting range of seismic supports and hangers:
Air conditioning units, fans and other equipment with gravity greater than 1.8kN in the suspension pipeline;
Gas pipeline above DN25;
Domestic water supply, fire-fighting pipelines above DN65, pipeline accessories with a flexible connection mass of 9kg ~ 25kg, and pipeline accessories with a rigid connection mass greater than 25kg;
Duct system with rectangular cross-sectional area greater than or equal to 0.38m2 and circular diameter greater than or equal to 0.7m;
For electrical piping with inner diameter greater than or equal to 60mm and cable ladder tray and bus duct with gravity greater than or equal to 150N/m;
All specifications of smoke and exhaust air duct and accident ventilation air duct and its equipment.
Selection of pipelines:
Water supply and drainage and fire fighting, heating, ventilation, air conditioning, gas, heat, electricity, communication;
Select according to pipe size or weight of different systems;
Can be set up single pipe, can also be set up multi-pipe co-frame integrated seismic support;
The provisions on page 41 of the specification state:
Equipment with gravity greater than 1.8KN in suspended pipeline;
Domestic water supply and fire-fighting piping system above DN65; (for water pipes)
Rectangular cross-sectional area greater than or equal to 0.38 square meters and circular diameter greater than or equal to 0.7m duct system;
For electrical piping with inner diameter greater than or equal to 60mm;
Cable ladder, cable tray and bus duct with gravity greater than or equal to 150N/m;
Gas pipeline with inner diameter greater than or equal to 25mm;
Bracket arrangement and related requirements:
Maximum spacing of seismic supports and hangers Table 8.2.3
The maximum seismic reinforcement spacing of the reconstruction works is half of the value in the above table;
Note: This table is the basic basis for the design of the layout plan of the seismic support, and it is also the core content of the seismic support design in the specification.
Can be read:
The spacing of anti-seismic supports is not necessarily the maximum spacing of pipeline types;
The spacing is related to the magnitude of seismic action, and when αEK is greater than 1.0, the bracket needs to be encrypted;
It is related to the angle of diagonal brace. When the vertical angle of diagonal brace is less than 45 degrees, the bracket shall be encrypted;
3.4.2 When calculating two mechanical and electrical equipment connected together with different seismic measures, the seismic design shall be carried out according to higher requirements. When the connection of building mechanical and electrical equipment is damaged, it shall not cause the failure of the auxiliary mechanical and electrical equipment with higher requirements connected to it.
Note: It is easy to understand that the comprehensive seismic support is calculated and fortified according to the pipeline with higher standard.
seismic hanger layout principle:
8.3.1 Each horizontal straight pipeline shall be provided with lateral seismic supports and hangers at both ends.
8.3.2 When the spacing between two lateral seismic supports and hangers exceeds the maximum design spacing, lateral seismic supports and hangers shall be added in the middle.
8.3.3 Each section of horizontal straight pipeline shall be provided with at least one longitudinal seismic support and hanger. When the distance between two longitudinal seismic supports and hangers exceeds the maximum design spacing, longitudinal seismic supports and hangers shall be added in turn according to the spacing required in Article 8.2.3 of this Code.
8.3.5 For horizontal pipes with rigid connection, the longitudinal offset between two adjacent seismic supports and hangers is allowed. The following provisions shall be met:
1 Water pipe and wire casing shall not exceed 1/16 of the maximum distance between lateral supports and hangers;
2 Ducts, cable ladders, cable trays and cable trays shall not exceed twice their width.
For example, the maximum offset calculation is 12/16=0.75 meters, which is very harsh.
8.3.6 Horizontal pipelines shall be provided with lateral seismic supports and hangers within 0.6m from the bend; if the diagonal brace acts directly on the pipeline, it can be used as the longitudinal seismic supports and hangers of the pipeline on the other side; the spacing from the next longitudinal seismic supports and hangers shall be calculated according to the following formula:
In the formula: L is the spacing from the next longitudinal seismic support and hanger (m);L1 is the spacing of longitudinal seismic support and hanger (m);L2 is the spacing of lateral seismic support and hanger (m).
For example: L1 = 24 meters, L2 = 12, then: calculate L = 18.6 meters
8.3.7 When horizontal pipeline is connected with ground equipment through vertical pipeline, flexible connection shall be adopted between pipeline and equipment. The horizontal pipeline shall be provided with lateral support within 600mm from the vertical pipeline. Seismic support shall be set for vertical pipeline bottom more than 0.15m from the ground.
3.4.4 The calculation method of seismic action of building mechanical and electrical engineering shall meet the following requirements:
The seismic force of each member and component shall be applied to its center of gravity, and the horizontal seismic force shall be in any horizontal direction;
The seismic action produced by the self-gravity of the building's electromechanical engineering can be calculated by the equivalent lateral force method; for the building's electromechanical engineering supported on different floors or on both sides of the seismic joint, in addition to the seismic action produced by the self-gravity, the action effect produced by the relative displacement between the support points during the earthquake should be calculated at the same time;
When the natural vibration period of the building mechanical and electrical equipment (including supports) is greater than 0.1s and its gravity exceeds 1% of the gravity of the floor where it is located, or when the gravity of the building mechanical and electrical equipment exceeds 10% of the gravity of the floor where it is located, it is appropriate to enter the overall structural model for seismic calculation, or it can be calculated by floor response spectrum method. Among them, the equipment connected with the floor inelastically can be directly included in the analysis of the whole structure as a particle to obtain the seismic action of the equipment.
The equivalent lateral force method is a simple and feasible method.
When the equivalent lateral force method is adopted, the standard value of horizontal seismic action shall be calculated according to the following formula:
F=ge1z2αmaxG (3.4.5)
F: Standard value of horizontal seismic action applied to the center of gravity of the M & E facilities in the most unfavorable direction;
γ: Function coefficient of non-structural member, as per Article 3.4.1 of this specification;
η: Category coefficient of non-structural member, subject to Article 3.4.1 of this specification;
ζ 1: state coefficient; 2.0 should be taken for any equipment and flexible system whose supporting point is lower than the centroid, and 1.0 should be taken for the rest; (here: 1.0 should be taken for all hangers)
ζ 2: position coefficient, the vertex of the building should be 2.0, the bottom should be 1.0, linear distribution along the height; (the basement of the building should be 1.0)
αmax: maximum value of seismic influence coefficient; it can be adopted according to the provisions of multiple earthquakes in Article 3.3.5 of this Code;
G: Section pipeline weight: 1) shall include the gravity of the pipeline and its rated load medium, 2) shall be included in the weight of the branch pipe;
Comprehensive coefficient of horizontal seismic force: αEk = γηζ 1 ζ 2 αmax
Note: The calculated αEk of seismic supports and hangers shall not be less than 0.5.
3.5.1 The basic combination of seismic action effects (including effects caused by self-gravity and effects caused by relative displacement of bearings) and other load effects of building mechanical and electrical engineering facilities engineering shall be calculated as S = γ GSGE γ EhSEhk (3.5.1)
S: design value of the combination of internal forces of the mechanical and electrical engineering facilities or components, including the combined bending moment, axial force and shear design value;
γG: partial coefficient of gravity load, generally, 1.2 shall be adopted;
γEh: is the partial coefficient of horizontal seismic action, taking 1.3;
Senk: effect of standard value of horizontal seismic action.
Note: In general, only horizontal earthquake action should be considered in the calculation of seismic support.
10.2.2 In the seismic checking calculation of mechanical and electrical engineering facilities, the friction force shall not be used as the resistance to resist the earthquake. The seismic adjustment coefficient of bearing capacity can be 1.0 and shall meet the following requirements: S≤R(R is the design value of bearing capacity of components)
Note: The bearing capacity of the seismic support is greater than the seismic action of the pipeline.
Bar stress: two kinds of bar stress states caused by horizontal force direction.
The force of the rod is transmitted to the structure by connecting fittings, vertical rods, diagonal braces and anchor bolts;
Brackets shall be designed to ensure connections (fittings, supports, etc.).
Strength checking calculation under seismic force
Checking calculation of strength of diagonal braces and seismic connecting members (check of compression and strength of fittings);
Checking calculation of strength of suspender;
Checking calculation of strength of each anchorage body, including diagonal brace anchor bolt, hanger anchor bolt, etc;
Checking calculation of tube bundle strength;
Provisions for support construction:
8.3.4 The distance between the diagonal brace of the seismic support and hanger shall not exceed 0.1m;
8.3.11 The vertical angle of diagonal bracing installation of lateral and longitudinal seismic supports and hangers should be 45 ° and not less than 30 °;
3.1.8 The construction mechanical and electrical engineering pipelines passing through the isolation layer shall adopt flexible connection or other effective measures, and seismic supports shall be set on both sides of the isolation layer.
8.3.13 When the pipeline laid along the wall is provided with brackets and supports entering the wall and the pipe clamp can fasten the circumference of the pipeline, it can be used as a lateral seismic support and hanger.
8.3.14 The setting of single pipe (pole) anti-seismic supports and hangers shall meet the following requirements:
1) The horizontal pipe connecting the riser shall be provided with the first anti-seismic hanger within 0.6m near the riser;
2) When the length of the riser exceeds 1.8m, four-way seismic supports and hangers shall be set at the top and bottom of the riser, and when the length is greater than 7.6m, seismic supports and hangers shall be added in the middle;
3) When the riser crosses the structural floor through the casing, the casing can restrict the horizontal movement of the pipeline and can be used as a horizontal four-way seismic support;
4) When the mass of the accessories installed in the pipeline exceeds 25kg, lateral and longitudinal seismic supports and hangers shall be set;
8.3.12 The installation of seismic hanger diagonal brace shall not deviate from its centerline by 2.5 °;
8.3.9 Seismic supports shall not be installed on non-structural main parts, such as light partition walls;
8.3.15 The setting of door-type seismic supports and hangers shall meet the following requirements:
1) The door-type seismic support and hanger shall have one lateral seismic support and hanger or two longitudinal seismic support and hanger;
2) The same load-bearing hanger shall be hung with multi-layer door-type hanger, and the load-bearing hanger shall be independently reinforced and provided with seismic bracing;
3) The lateral and longitudinal diagonal braces of door-type seismic supports and hangers shall be installed at the connection of upper beam or load-bearing hanger;
4) When the mass of the accessories on the pipeline exceeds 25kg and is rigidly connected with the pipeline, or when the mass of the accessories is 9kg ~ 25kg and is flexibly connected with the pipeline, lateral and longitudinal seismic supports and hangers shall be set;
Code for Seismic Design of Mechanical and Electrical Engineering of GB-50981-2014 Buildings
Article 8.1.2 stipulates that all components of seismic supports and hangers shall be finished components, and the structure of connecting fasteners shall be easy to install.
Article 3.5.2 stipulates: seismic checking calculation for construction of mechanical and electrical engineering facilities
Article 3.3.2 of the code for seismic design of JGJ339-2015 non-structural members
RELATED INFORMATION
The 2022 "Xi Jiu Enters Famous Enterprises" Series of Activities Entering CHINESTAR Group
2022-10-14
2022-09-01
Xiaochen Is Here! The Group's Cartoon Image Has Been Officially Launched
2022-08-31
Address: 14th Floor, Nature Home Building, No.1 Zhicheng Road, Daliang Street, Shunde District, Foshan City, Guangdong Province, China
Telephone: 86-757-22236808/22615959
Customer service hotline: 86-400-6683686
E-mail:fszcgg@126.com
WeChat Public Number
Sweep to learn more