What is seismic bracket? What is the role of seismic bracket?


Abstract

Seismic supports and hangers are used to support water pipes, air pipes, bridges and other mechanical and electrical pipeline equipment and provide seismic support

In the construction of mechanical and electrical engineering, seismic supports and hangers have been forced to use, but many engineering friends are still relatively unfamiliar with this, because the construction has been basically not considered in the design of mechanical and electrical seismic, seismic supports and hangers have never been used. But now the situation is different. The construction electromechanical industry has a national standard in the field of seismic resistance, which clearly stipulates the setting and design of seismic supports.

中辰

The following is a comb for seismic supports and hangers

What is the basis for setting up seismic supports and hangers?

What is seismic support and hanger?

What are the common forms of seismic supports and hangers?

Where do you need to use seismic supports and hangers?

中辰

What is the basis for setting up seismic supports and hangers?

According to the national standard GB50981-2014 "Code for Seismic Design of Building Electromechanical Engineering" issued and implemented by the Ministry of Housing and Urban-Rural Development in 2015, the design and use of seismic supports and hangers are clearly stipulated. The standard has been implemented since August 1, 2015, which also means that seismic supports and hangers must be considered in the mechanical and electrical engineering of buildings since then.

What is seismic support and hanger?

Seismic supports and hangers are used to support water pipes, air pipes, bridges and other mechanical and electrical pipeline equipment and provide seismic support products. According to the GB50981-2014 "Code for Seismic Design of Building Mechanical and Electrical Engineering", the definition of seismic support and hanger is: a seismic support facility that is firmly connected with the building structure and takes seismic force as the main load. It is composed of anchor body, reinforced hanger rod, seismic connecting member and seismic diagonal brace.

What are the common forms of seismic supports and hangers?

According to the GB50981-2014 Code for Seismic Design of Building Mechanical and Electrical Engineering, the seismic support and hanger is composed of anchors, reinforced hanger rods, seismic connection components and seismic bracing. All components of anti-seismic supports and hangers shall be finished components, and the structure of connecting fasteners shall be convenient for installation.

中辰

中辰

Lateral seismic hanger

To resist the lateral horizontal seismic force.

中辰

Longitudinal seismic hanger

To resist the vertical horizontal seismic force.

中辰

Single pipe (pole) anti-seismic support and hanger

It is an anti-seismic support hanger composed of a load-bearing hanger and an anti-seismic diagonal brace.

中辰

Door-type seismic supports and hangers

Seismic supports and hangers composed of two or more load-bearing hangers, beams and seismic braces.

中辰

Where do you need to use seismic supports and hangers?

According to the GB50981-2014 Code for Seismic Design of Mechanical and Electrical Engineering of Buildings:

Article 1.0.4 (strong article) stipulates that seismic design must be carried out for building mechanical and electrical engineering in areas with seismic design intensity of 6 degrees and above.

The provisions of Article 3.1.6 specify the contents of seismic fortification:

① Suspend the equipment with gravity greater than 1.8kN in the pipeline;

② Domestic water supply and fire-fighting piping system above DN65;

③ Duct system with rectangular cross-sectional area greater than or equal to 0.38 ㎡ and circular diameter greater than or equal to 0.7m;

④ For electrical piping with inner diameter greater than or equal to 60mm and cable ladder, cable tray and bus duct with gravity greater than or equal to 150N/m.

Article 3.1.8 stipulates that the construction mechanical and electrical engineering pipeline passing through the isolation layer shall be flexibly connected or otherwise, and seismic supports shall be set on both sides of the isolation layer.

Article 4.1.2.1 stipulates that when the straight length of water supply and drainage risers of high-rise buildings in 8-degree and 9-degree areas is greater than 50m, anti-vibration measures should be taken. When the straight length is greater than 100m, anti-vibration measures shall be taken.

Article 4.1.2.3 requires fortification of indoor water supply, hot water and fire pipeline diameter greater than or equal to DN65 horizontal pipeline, when it is fixed by hanger, bracket or bracket, seismic support shall be set as required.

Article 5.1.2.4 stipulates that the pipelines in the boiler room, refrigeration room and heat exchange station shall have reliable lateral and longitudinal seismic support. Multiple pipes share supports and hangers or single pipe supports and hangers with pipe diameter greater than or equal to 300mm, and door-type seismic supports and hangers should be adopted.

Article 5.1.3.3 stipulates that seismic supports and hangers can be used for air ducts with rectangular cross-sectional area greater than or equal to 0.38 ㎡ and circular diameter greater than or equal to 0.70m.

Article 5.1.4 (Strong Article) stipulates that anti-seismic supports and hangers shall be used for smoke exhaust duct, accident ventilation duct and related equipment.

Article 5.1.5.4 stipulates that air conditioning units, fans and other equipment with gravity greater than 1.8kN should not be hoisted and installed. When hoisting is necessary, it should be avoided to be set above the position of personnel movement and evacuation passage, but seismic supports and hangers should be set.

Article 6.1.1 stipulates that the gas pipeline with an inner diameter greater than or equal to 25mm shall be subject to seismic design, and the installation of seismic supports and hangers of the pipeline shall comply with the regulations.

Article 6.2.8 stipulates that in buildings with a building height greater than 50m, the gas pipeline shall be provided with seismic supports at appropriate intervals according to the seismic requirements of the building.

Article 7.1.2 stipulates that the electrical piping with an inner diameter of not less than 60mm and the cable ladder, cable tray and bus duct with a gravity of not less than 150N/m shall be subject to seismic fortification.

Source: content from the network copyright owned by the original author

RELATED INFORMATION


The 2022 "Xi Jiu Enters Famous Enterprises" Series of Activities Entering CHINESTAR Group

2022-10-14

A Gentleman's Quality Oriental Xi Jiu 2022 "Xi Jiu Enters Famous Enterprises" Series of Activities Entering CHINESTAR Group

Good News! The Construction Project Undertaken by CHINESTAR Won the Guangdong Province Construction Engineering Golden Craftsman Award and Quality Award

2022-09-01

Warm congratulations to the company for winning the Golden Craftsman Award and Quality Award! The achievement of the highest provincial award fully demonstrates CHINESTAR's excellent technological innovation ability and excellent engineering construction level, demonstrating the company's rich construction experience and strong construction strength in organizing, implementing, and ensuring major projects.

Xiaochen Is Here! The Group's Cartoon Image Has Been Officially Launched

2022-08-31

Faced with a new starting point and a new journey, CHINESTAR will carry on the past and seize opportunities, forge ahead with determination, and Xiaochen will work together with us to write a new chapter of high-quality development!